Technical Specifications - T10KL Basic datasheet_En

Parameter Value
Model T10KL BASIC
Capacity 10kVA / 9kW
Input
Nominal voltage 208/220/230/240 V AC, L+N+PE
Voltage range 110~300 V AC
Frequency range 50/60 +/- 6 Hz
Power factor >= 0.99
THDi (Total Harmonic Distortion of current) <= 5% (linear load); <= 8% (non-linear load)
Output
Nominal voltage 208/220/230/240 V AC, L+N+PE
Voltage accuracy +/- 1%
Frequency 50/60 Hz +/- 0.1%
THDu (Total Harmonic Distortion of voltage) <= 2% (linear load); <= 5% (non-linear load)
Transfer time Zero
Waveform Pure sine wave
Crest factor 3:1
Overload capacity (Linear mode) Load 102%~105%, 30 min; load 105%~125%, 10 min; Load 125–150%, 30 s; load >150%, 500 ms
Overload capacity (Battery mode) Load 102%~105%, 10 min; load 105%~125%, 1 min; Load 125–150%, 10 s; load >150%, 500 ms
Efficiency
Linear mode 95%
Battery mode 94.50%
ECO mode 98%
Battery
Nominal voltage 144 V DC
Battery quantity 9Ah * 14 pcs.
Charge current 1A (1-12A)
Interface RS232 / USB / SNMP card (optional) / AS400 card (optional) / RS485 card (optional)
Operating Conditions
Operating temperature 0~40°C
Humidity 0–95% (non-condensing)
Noise level <= 50 dB at 1 meter distance
Installation height < 1000 m without power derating
Physical Parameters
Dimensions (WDH) mm 190 * 437 * 322
Weight (kg) 11
  1. Office and Server Equipment
  2. Medical facilities and laboratories
  3. Telecommunications Systems

① RS232
② Smart slot
③ Fan
④ USB
⑤ Input circuit breaker
⑥ Service (bypass) circuit
breaker (optional)
⑦ Terminal block
⑧ Output circuit breaker (optional)
⑨ EPO (Emergency Power Off)
⑩ Maintenance status
⑪ Battery circuit breaker (optional)
⑫ External battery connection port (optional)

Преимущества
High efficiency — up to 95% conversion efficiency of the variable current in the mains mode and 94.5% in the battery life as well as 98% efficiency in ECO mode.
Wide input voltage range — uninterrupted operation in the input range voltage from 110 V AC to 300 V alternating current, which provides a high adaptability to different power supply conditions.
Power Factor Correction (PFC) Technology provides input power factor >99% and low non-linear distortion (THDi) (≤5% for linear loads, ≤8% for non-linear loads), which guarantees compatibility with modern power supply systems.
DSP technology uses digital processing signals to ensure high performance and reliability, providing an output signal in view of a pure sinusoid with voltage precision ±1% and non-linear distortion factor THDu ≤2% for linear loads.
Intelligent monitoring and control includes an intelligent RS232/USB port with monitoring software, and also optional SNMP, RS485 and AS400 for advanced remote control.
Flexible battery options that allow use both internal and external batteries to increase battery life work.
Sophisticated design with automatic fan speed control, function emergency Power Off (EPO) and Extended the ability to work with overloads provides stable and reliable operation of the system.
Maintains operation with generators and battery cold start function, which guarantees a stable and continuous operation even in unstable or missing power supply.
Advantages
High efficiency — up to 95% conversion efficiency of the variable current in the mains mode and 94.5% in the battery life as well as 98% efficiency in ECO mode.
Wide input voltage range — uninterrupted operation in the input range voltage from 110 V AC to 300 V alternating current, which provides a high adaptability to different power supply conditions.
Power Factor Correction (PFC) Technology provides input power factor >99% and low non-linear distortion (THDi) (≤5% for linear loads, ≤8% for non-linear loads), which guarantees compatibility with modern power supply systems.
DSP technology uses digital processing signals to ensure high performance and reliability, providing an output signal in view of a pure sinusoid with voltage precision ±1% and non-linear distortion factor THDu ≤2% for linear loads.
Intelligent monitoring and control includes an intelligent RS232/USB port with monitoring software, and also optional SNMP, RS485 and AS400 for advanced remote control.
Flexible battery options that allow use both internal and external batteries to increase battery life work.
Sophisticated design with automatic fan speed control, function emergency Power Off (EPO) and Extended the ability to work with overloads provides stable and reliable operation of the system.
Maintains operation with generators and battery cold start function, which guarantees a stable and continuous operation even in unstable or missing power supply.