| MODEL |
M60 |
| Capacity |
| Frame |
60 kVA |
| Module |
15 kVA |
| Number of modules |
4 |
| Input |
| Phase |
3 phases, 4 wires and ground |
| Nominal voltage |
380/400/415 VAC |
| Voltage range |
138–485 VAC |
| Operation at 40°C |
UPS operates at full load at 323–485 VAC and operates with derated capacity at 323–138 VAC |
| Operation at 30°C |
UPS operates at full load at 305–485 VAC and operates with derated capacity at 305–138 VAC |
| Frequency range |
40/70 Hz |
| Input power factor |
≥0.99 |
| Total harmonic distortion of current (THDi) |
≤3% (full linear load), ≤ 5% (at 100% non-linear load) |
| Bypass voltage range |
Max. voltage: 220V: +25% (optional +10%, +15%, +20%); 230V: +20% (optional +10%, +15%); 240V: +15% (optional +10%). Min. voltage: -45% (optional -20%, -30%) |
| Frequency protection range |
±10% |
| Generator connection |
Yes |
| Battery |
| Voltage |
±180V / 192V / ±204V / ±216V / ±228V / ±240V / ±252V / ±264V / ±276V / ±288V / ±300V VDC (30/32/34/36/38/40/42/44/46/48/50 pcs., optional) |
| Charging current (UPS Cabinet) |
40 A max. |
| Charging current (UPS Module) |
5 A max. |
| Output |
| Phase |
3 phases, 4 wires and ground |
| Nominal voltage |
380/400/415 VAC |
| Power factor |
1 |
| Voltage regulation |
1% |
| Crest factor |
3:1 |
| Total harmonic distortion (THD) |
≤ 2% with linear load, ≤ 4% with non-linear load |
| Efficiency |
96% |
| Overload |
≤ 110%, transfer to bypass after 60 min; ≤ 125%, transfer to bypass after 10 min; ≤ 150%, transfer to bypass after 1 min |
| Frequency in line mode |
±1% / ±2% / ±4% / ±5% / ±10% of nominal frequency (optional) |
| Frequency in battery mode |
50/60 Hz ± 0.1% |
| Transfer time |
Line → Battery: 0 ms; Line → Bypass: 0 ms |
| Protection |
| Alarm |
overload, mains failure, UPS fault, low battery, etc. |
| Protection |
short circuit, overload, overtemperature, low battery, fan fault |
| Communication Interfaces |
RS485, dry contact, SNMP card (optional) |
| Operating Conditions |
| Operating temperature |
0~40°C (operation) |
| Storage temperature |
-25°C ~ 55°C (without battery) |
| Humidity |
0–95% (non-condensing) |
| Installation altitude |
< 1500 m |
| Noise |
<70 dB |
| Physical Parameters |
| Dimensions (DWH) mm (Frame) |
850×485×827 |
| Dimensions (DWH) mm (Module) |
620×440×86 |
| Weight (kg) (Frame) |
75 kg |
| Weight (kg) (Module) |
19.5 kg |
| Standards |
EN62040–1, EN62040–2, EN62040–3 |