High-quality products at affordable prices, direct from the manufacturer

ARIET ARIKSO LT3315S

The ARIKSO UPS uses online double-conversion technology, which completely eliminates all types of power grid issues and provides customers with a stable and pure sine-wave power supply.

Application

Description

The ARIKSO UPS uses online double-conversion technology, which completely eliminates all types of power grid issues and provides customers with a stable and pure sine-wave power supply.

The innovative design ensures these products offer unmatched reliability and high performance. A high input power factor and low input current harmonics guarantee the UPS’s environmental friendliness and safety, while high efficiency ensures energy savings.

Technical Specifications - LT3310-40S datasheet_En

Parameter LT3310S LT3315S LT3320S LT3330S LT3340S
Power (at cos φ = 1.0) 10 kVA 15 kVA 20 kVA 30 kVA 40 kVA
Input
Phase 3 phases, 4 wires + ground
Nominal voltage 380 / 400 / 415 V AC
Voltage range 138 ~ 485 V AC
Frequency range 40 ~ 70 Hz
Power factor (input) >= 0.99
Harmonic distortion (THDi) <= 3% (100% non-linear load)
Output
Output voltage 380 / 400 / 415 V AC
Power factor (output) 1.0
Voltage regulation ± 1%
Output frequency 50 / 60 Hz
Waveform Pure sine wave
Overload capacity 110% — 60 min; 125% — 10 min; 150% — 1 min
Efficiency up to 95%
Crest factor 3:1
Battery
Configuration With external batteries
Battery voltage Optional, standard range 240V, built-in 30-40 pcs. 7/9Ah batteries Optional, standard range 240V, built-in 80 pcs. 7/9Ah batteries
Battery management Intelligent system for extending battery service life
Battery charge current Max. 10 A
Interfaces
Ports USB, RS232, RS485, Parallel port, REPO port, LBS port (optional), Backfeed port, Intelligent slot, SNMP
Parallel operation board Built into UPS
Operating Conditions
Operating temperature 0 ~ 40°C
Storage temperature -25 ~ 55°C (without battery)
Relative humidity 0 ~ 95% (non-condensing)
Installation height < 1500 m
Noise level < 55 dB
Protection Short circuit, overload, overheating, low battery charge, others
Physical Parameters
Dimensions (WDH), mm 790*280*720 950*400*985 950*400*985 950*400*985 950*400*985
Dry weight, kg (without batteries) 53.5 54 54.5 55.5 60.5

*Note: The ← arrow indicates that the parameter value is exactly the same as the value in the column to the left.

  1. Office and Server Equipment
  2. Switches and Networking Devices
  3. Telecommunications Systems
Преимущества
Wide input voltage range — the device automatically adapts to unstable and “rough” power grids.
DSP technology significantly improves system reliability and operational stability.
User-friendly interface — simple controls and easy operation.
Intelligent battery management — optimizes charge/discharge cycles and extends battery life.
Online double-conversion technology — provides the highest level of power supply protection through continuous energy conversion using an AC–DC–AC circuit.
N+X redundancy — the system consists of the minimum number of power modules required to supply the load.
Output power factor 0.9 — the device is capable of delivering a large portion of its rated power as active power.
Communication interfaces — RS485/relay card/USB/SNMP option; the availability of various communication interfaces ensures easy connection of the device to monitoring systems.
Advantages
Wide input voltage range — the device automatically adapts to unstable and “rough” power grids.
DSP technology significantly improves system reliability and operational stability.
User-friendly interface — simple controls and easy operation.
Intelligent battery management — optimizes charge/discharge cycles and extends battery life.
Online double-conversion technology — provides the highest level of power supply protection through continuous energy conversion using an AC–DC–AC circuit.
N+X redundancy — the system consists of the minimum number of power modules required to supply the load.
Output power factor 0.9 — the device is capable of delivering a large portion of its rated power as active power.
Communication interfaces — RS485/relay card/USB/SNMP option; the availability of various communication interfaces ensures easy connection of the device to monitoring systems.